The fixed capacitor CLMD is particularly suitable for on-site compensation, i.e. directly on the electrical devices that generate reactive power (e.g. electric motors, transformers). e.g. electric motors, transformers). It can also be used where high mechanical demands are placed on the capacitors.
The power capacitor CLMD consists of a number of single-phase round of single-phase round windings made of a metallised plastic film. Each element contains an internal winding fuse according to the IPE principle. The individual self-healing capacitor elements are fitted with cooling plates in a common sheet steel housing with flame-retardant granulate filling. granulate filling.
|
|
|
|
|
Schutzart: IP 42 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Nennleistung kvar |
Bestellbezeichnung |
Nenn- strom* A |
NH-Siche- rungen träge A |
Maße** (B x T x H) mm |
Gewicht ca. kg |
Artikel- nummer |
|||
|
|
|
|
|
|
|
|
|
|
Nennspannung 400 V, 50 Hz Drehstrom | |||||||||
|
|
|
|
|
|
|
|
|
|
5 | CLMD 13 - | 400 / | 50 - | 5 | 7 | 16 | 182 x 80 x 262 | 2 | C161-OAB |
6,7 | CLMD 13 - | 400 / | 50 - | 6,7 | 10 | 16 | 182 x 80 x 262 | 2 | C161-OAC |
10 | CLMD 13 - | 400 / | 50 - | 10 | 12 | 25 | 182 x 80 x 262 | 2 | C161-OAD |
12,5 | CLMD 13 - | 400 / | 50 - | 12,5 | 14 | 35 | 182 x 80 x 262 | 2 | C161-OAE |
15 | CLMD 13 - | 400 / | 50 - | 15 | 18 | 35 | 182 x 80 x 262 | 2 | C161-OAF |
16,7 | CLMD 43 - | 400 / | 50 - | 16,7 | 24 | 35 | 176 x 152 x 275 | 7 | C161-OAG |
20 | CLMD 43 - | 400 / | 50 - | 20 | 29 | 50 | 176 x 152 x 275 | 7 | C161-OAH |
25 | CLMD 43 - | 400 / | 50 - | 25 | 36 | 63 | 176 x 152 x 275 | 8 | C161-OAK |
30 | CLMD 43 - | 400 / | 50- | 30 | 43 | 63 | 346 x 152 x 310 | 9 | C161-OAL |
35 | CLMD 43 - | 400 / | 50- | 35 | 51 | 80 | 346 x 152 x 310 | 10 | C161-OAM |
40 | CLMD 43 - | 400 / | 50- | 40 | 58 | 100 | 346 x 152 x 310 | 11 | C161-OAN |
50 | CLMD 63 - | 400 / | 50- | 50 | 72 | 125 | 346 x 152 x 485 | 15 | C161-OAP |
60 | CLMD 63 - | 400 / | 50- | 60 | 87 | 125 | 346 x 152 x 485 | 17 | C161-OAR |
70 | CLMD 63 - | 400 / | 50- | 70 | 101 | 160 | 346 x 152 x 485 | 18 | C161-OAS |
80 | CLMD 63 - | 400 / | 50- | 80 | 115 | 200 | 346 x 152 x 485 | 23 | C161-OAT |
100 | CLMD 83 - | 400 / | 50- | 100 | 144 | 200 | 346 x 152 x 670 | 25 | C161-OAU |
120 | CLMD 83 - | 400 / | 50- | 120 | 173 | 250 | 346 x 152 x 670 | 27 | C161-OAV |
|
|
|
|
|
|
|
|
|
|
Nennspannung 525 V, 50 Hz Drehstrom | |||||||||
|
|
|
|
|
|
|
|
|
|
10 | CLMD 13- | 525 / | 50- | 10 | 11 | 16 | 182 x 80 x 262 | 2 | C161-OCA |
20 | CLMD 43- | 525 / | 50- | 20 | 22 | 35 | 176 x 152 x 275 | 6 | C161-OCB |
30 | CLMD 53- | 525 / | 50- | 30 | 33 | 50 | 346 x 152 x 310 | 9 | C161-OCC |
40 | CLMD 53- | 525 / | 50- | 40 | 44 | 63 | 346 x 152 x 310 | 11 | C161-OCD |
50 | CLMD 63- | 525 / | 50- | 50 | 55 | 80 | 346 x 152 x 485 | 15 | C161-OCE |
60 | CLMD 63- | 525 / | 50- | 60 | 66 | 100 | 346 x 152 x 485 | 17 | C161-OCF |
80 | CLMD 63- | 525 / | 50- | 80 | 88 | 160 | 346 x 152 x 485 | 23 | C161-OCG |
100 | CLMD 83- | 525 / | 50- | 100 | 110 | 160 | 346 x 152 x 670 | 25 | C161-OCH |
120 | CLMD 83- | 525 / | 50- | 120 | 132 | 200 | 346 x 152 x 670 | 27 | C161-OCK |
|
|
|
|
|
|
|
|
|
|
Nennspannung 690 V, 50 Hz Drehstrom | |||||||||
|
|
|
|
|
|
|
|
|
|
5 | CLMD 13- | 690 / | 50- | 5 | 4 | 16 | 182 x 80 x 262 | 2 | C161-OEA |
10 | CLMD 13- | 690 / | 50- | 10 | 8 | 16 | 182 x 80 x 262 | 2 | C161-OEB |
15 | CLMD 13- | 690 / | 50- | 15 | 13 | 20 | 182 x 80 x 262 | 2 | C161-OEC |
20 | CLMD 43- | 690 / | 50- | 20 | 17 | 25 | 176 x 152 x 275 | 9 | C161-OED |
30 | CLMD 53- | 690 / | 50- | 30 | 25 | 50 | 346 x 152 x 310 | 11 | C161-OEE |
40 | CLMD 53- | 690 / | 50- | 40 | 33 | 50 | 346 x 152 x 310 | 19 | C161-OEF |
50 | CLMD 63- | 690 / | 50- | 50 | 42 | 63 | 346 x 152 x 485 | 23 | C161-OEG |
70 | CLMD 63- | 690 / | 50- | 70 | 59 | 100 | 346 x 152 x 485 | 25 | C161- OEH |
80 | CLMD 63- | 690 / | 50- | 80 | 67 | 100 | 346 x 152 x 485 | 27 | C161- OEK |
100 | CLMD 83- | 690 / | 50- | 100 | 84 | 125 | 346 x 152 x 670 | 29 | C161-OEL |
|
|
|
|
|
|
|
|
|
|
* For connection cross-sections, see explanations NH fuses and connection cross-sections. | |||||||||
** Dimensions without foot bracket | |||||||||
|
|
|
|
|
|
|
|
|
|
Unloading time: | |||||||||
Within 3 minutes after switching off to 75 V. | |||||||||