Scope of application

The CLMM-C6/-C8 and CDMM-C6/-C8 compensation modules can be used for both for use as centralised or decentralised compensation. The can be installed in any cabinet system. Adaptation to the to the power requirement can be easily made at any time.

Description

The compensation modules are available as choked modules with built-on filter circuit chokes. The modules are attached using two two guide rails (to be ordered separately), which are mounted side of the control cabinet. For mounting the guide rails the necessary kits are available depending on the enclosure type, and mounting brackets (incl. screws) are available for mounting the guide rails, depending on the enclosure type. The module is then pushed into the enclosure like a drawer. The modules are connected to each other via busbar lugs (included in delivery). with each other. When installing the modules, the max. permitted temperatures must be observed. Information on this can be found in the installation and operating instructions. As a rule, the use of one use of one fan module per enclosure. It contains the necessary control terminal strip for a complete system. The use of standard control cables (see accessories for compensation modules C6/C8) facilitates the necessary wiring of the auxiliary circuits.

Advantages





















Schutzart: IP 00, Nennspannung 400 V, 50 Hz Drehstrom




















Nenn-leistung
kvar

Stufen-
leistung
kvar
Bestellbezeichnung Nenn-
strom*
A

Maße
(B x T x H)
mm
Gewicht

ca. kg
Artikel-
Nummer





















Kompensationsmodule C8.4, Verdrosselung: p = 7%




















12.5
1 x 12.5 CLMM - 400/50 - 1 x 12.5 - L070-C8.4.3 18
694 x 380 x 295 30 F168 - A T A
25.0
2 x 12.5 CLMM - 400/50 - 2 x 12.5 - L070-C8.4.3 36
694 x 380 x 295 45 F168 - A T B
25
1 x 25 CLMM - 400/50 - 1 x 25 - L070-C8.4.3 36
694 x 380 x 295 35 F168 - A T C
37.5
12.5 + 25 CLMM - 400/50 - 12.5 + 25 - L070-C8.4.3 54
694 x 380 x 295 55 F168 - A T D
50
2 x 25 CLMM - 400/50 - 2 x 25 - L070-C8.4.3 72
694 x 380 x 295 60 F168 - A T E
50
1 x 50 CLMM - 400/50 - 1 x 50 - L070-C8.4.3 72
694 x 380 x 295 50 F168 - A T F




















Kompensationsmodule C8.4, Verdrosselung: p = 12,5%




















12.5
1 x 12.5 CLMM - 400/50 - 1 x 12.5 - L125-C8.4.3 18
694 x 380 x 295 30 F168 - A U A
25
1 x 25 CLMM - 400/50 - 1 x 25 - L125-C8.4.3 36
694 x 380 x 295 45 F168 - A U B




















Kompensationsmodule C8.4, Verdrosselung: p = LL1 (Kombifilter)




















25
2 x 12.5 CLMM - 400/50 - 2 x 12.5 - LL1-C8.4.3 36
694 x 380 x 295 50 F168 - A V A




















Kompensationsmodule C6.4, Verdrosselung: p = 7%




















12.5
1 x 12.5 CLMM - 400/50 - 1 x 12.5 - L070-C6.4.3 18
494 x 380 x 295 30 F168 - A N A
25.0
2 x 12.5 CLMM - 400/50 - 2 x 12.5 - L070-C6.4.3 36
494 x 380 x 295 45 F168 - A N B
25
1 x 25 CLMM - 400/50 - 1 x 25 - L070-C6.4.3 36
494 x 380 x 295 35 F168 - A N C
37.5
12.5 + 25 CLMM - 400/50 - 12.5 + 25 - L070-C6.4.4 54
494 x 380 x 395 55 F168 - A N D
50
2 x 25 CLMM - 400/50 - 2 x 25 - L070-C6.4.4 72
494 x 380 x 395 60 F168 - A N E
50
1 x 50 CLMM - 400/50 - 1 x 50 - L070-C6.4.4 72
494 x 380 x 395 50 F168 - A N F




















Kompensationsmodule C6.4, Verdrosselung: p = 12,5%




















12.5
1 x 12.5 CLMM - 400/50 - 1 x 12.5 - L125-C6.4.4 18
494 x 380 x 295 30 F168 - A P A
25
1 x 25.0 CLMM - 400/50 - 1 x 25.0 - L125-C6.4.4 36
494 x 380 x 395 45 F168 - A P B




















Kompensationsmodule C6.4, Verdrosselung: p = LL1 (Kombifilter)




















25
2 x 12.5 CLMM - 400/50 - 2 x 12.5 - LL1-C6.4.4 36
494 x 380 x 395 50 F168 - A R A




















* Anschlussquerschnitte siehe Erläuterungen NH-Sicherungen und Anschlussquerschnitte.




















Anmerkungen:
Die Bestellbezeichnung z. B. ….-C6.6.3, gibt einen Hinweis auf die Moduleinbaumaße.
Der erste Zahl (6) kennzeichnet eine Schrankbreite von 600 mm. Die zweite Zahl (6) kennzeichnet
eine Schranktiefe von 600 mm. Die dritte Zahl (3) gibt die Planhöhe des Moduls an hier 300 mm.
Achtung! Bitte beachten Sie die Modulabmessungen beim Planen einer Anlage.